Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00328
Parcel: 107142180

Address:
231 W ALTURAS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00328
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/16/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 3/10/04
ACTIVITY NUMBER: TO4CM00328
PROJECT NAME: STEEL CANOPY
PROJECT ADDRESS: 231 W. ALTURAS ST.
ARCHITECT / ENGINEER: JOHN JAMES GLANCY & MUHAMMAD ALMAHAYNI
PROJECT REVIEWER: CHRISTY FOREMAN
PHONE: 791-5550 X1108
EMAIL: CFOREMA1@CI.TUCSON.AZ.US

TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

Christy Foreman called and left message with Aaron Construction Company, please review 2003 IBC for code sections below. Drawings addressing code items need to be provided by a Arizona registered Architect or Engineer.
1) PROVIDE A COMPLETED CODE ANALYSIS DATA SHEET FOR COMBINATION OF LOTS.
CHAPT.3 - 303-312 OCCUPANCIES, 302.3.1 NONSEPERATED USES EACH PORTION OF THE BUILDING SHALL BE INDIVIDUALLY CLASSIFIED AS TO USE. THE REQUIRED TYPE OF CONSTRUCTION FOR THE BUILDING SHALL BE DETERMINED BY APPLYING THE HEIGHT AND AREA LIMITATIONS FOR EACH OF THE APPLICABLE OCCUPANCIES TO THE ENTIRE BUILDING. THE MOST RESTRICTIVE TYPE OF CONSTRUCTION SO DETERMINED SHALL APPLY TO ENTIRE BUILDING. ALL OTHER CODE REQUIREMENTS SHALL APPLY TO EACH PORTION OF THE BUILDINGBASED ON THE USE OF THAT SPACE, EXCEPT THAT THE MOST RESTRICTIVE APPLICABLE PROVISIONS OF SECTION 403 AND CHAPTER 9 SHALL APPLY TO THESE NONSEPERATED USES., 302.3.3 - EACH PORTION OF A BUILDING SHALL BE INDIVIDUALLY CLASSIFIED AS TO USE AND SHALL BE COMPLETELY SEPERATED FROM ADJACENT AREAS BY FIRE BARRIER WALLS OR HORIZONATAL ASSEMBLIES OR BOTH HAVING A FIRE RESISTANCE RATING DETERMINED IN ACCORDANCE WITH TABLE 302.3.3.

CHAPT. 5 GENERAL BLDG. HEIGHTS AND AREAS - TABLE 03 ALLOWABLE HEIGHT AND BUILDING AREAS, 503.1.3 BUILDINGS ON THE SAME LOT. TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS 504 & 506.

CHAPT. 6 TYPES OF CONSTRUCTION - TABLE 602 FIRE RESISTIVE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPERATION DISTANCE.

CHAPT. 7 -704.3 BUILDINGS ON THE SAME PROPERTY SHALL BE ASSUMED TO HAVE A PROPERTY LINE BETWEEN THEM.

2) PROVIDE A SITE PLAN THAT REFLECTS THE COMBINATION OF LOTS AND ADDRESSES. CLARIFY ON SITE PLAN THAT IBC CHAPT. 11 REQUIREMENTS HAVE BEEN MET. SUCH AS PUBLIC WAY, ROUTE OF TRAVEL, AND PARKING.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
04/15/2005 SUE REEVES REJECT SHELF Completed