Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00328
Parcel: 107142180

Address:
231 W ALTURAS ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM00328
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2004 JIM TATE ENGINEERING REVIEW Denied A copy of the stamped approved Site Plan must be included in the submittal.
08/05/2004 Jim Egan FIRE REVIEW Approved
08/26/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please submit lighting fixture cut sheet. Need to verify suitability for damp location and compliance with Lighting Ordinance.
2. Only one feeder or branch circuited is permitted to a separate building per NEC 225.30.
3. Demonstrate compliance with NEC 250.32 for two or more buildings supplied by a common service.
4. Fill in load for new lighting on panel schedule. Complete panel schedule load calculations to include new lighting.
5. Lights on Ckt 17 are on a 2-pole circuit feeding Office Air Handler. Pls clarify.
6. One-Line Diagram indicates new electrical conduit to new power pole. Please distinguish new from existing equipment. If all equipment is new, then all electrical loads, such as warehouse receptacles and lighting and appliances and HVAC units, have to be located on plan view and identified by panel and circuit numbers. If service is new, provide TEP available fault current and fault calculations.
08/27/2004 Daniel Castro ZONING REVIEW Denied Building plans may not be reviewed and approved until the site plan is approved.
08/30/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 9/1/04
ACTIVITY NUMBER: TO4CM00328
PROJECT NAME: STEEL CANOPY
PROJECT ADDRESS: 231 W. ALTURAS ST.
ARCHITECT / ENGINEER: JOHN JAMES GLANCY & MUHAMMAD ALMAHAYNI
PROJECT REVIEWER: CHRISTY FOREMAN
PHONE: 791-5550 X1108
EMAIL: CFOREMA1@CI.TUCSON.AZ.US

TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) PROVIDE A COMPLETED CODE ANALYSIS DATA SHEET FOR COMBINATION OF LOTS.
2) PROVIDE A SITE PLAN THAT REFLECTS THE COMBINATION OF LOTS AND ADDRESSES. CLARIFY ON SITE PLAN THAT IBC CHAPT. 11 REQUIREMENTS HAVE BEEN MET. SUCH AS PUBLIC WAY, ROUTE OF TRAVEL, AND PARKING.
3) REINFORCEMENT - CLARIFY GRADE 60 OR GRADE 40. CONFLICT BETWEEN DRAWINGS AND STRUCTURAL CALCULATIONS.
4) SOIL SHT. F1 = 1500 PSF WITH NO REPORT. SHT. 1 STRUCTURL CALCS = 200 PSF WITH NO REPORT. PLEASE CLARIFY WHICH WILL BE USED FOR PROJECT.
5) PLEASE COORDINATE STRUCTURAL CALCULATIONS AND STRUCTURAL MEMBERS WITH DRAWINGS. CLARIFICATION / RELATIONSHIP IS REQUIRED BETWEEN THE CALCULATIONS AND PLACEMENT / LOCATION OF STRUCTURAL MEMBERS.
6) WALL PANELS? DETAILS NOTE WALL PANELS. ELEVATIONS DO NOT SHOW WALL PANELS. PLEASE CLARIFY.
7) SPECIAL INSPECTION REQUIRED FOR FIELD WELDS.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2004 BETH GRANT OUT TO CUSTOMER Completed
09/08/2004 ANGIE SHOFFSTALL REJECT SHELF Completed