Permit Number: T04CM00309
Parcel: 133153410

Address:
1857 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00309
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2004 JIM EGAN FIRE REVIEW Approved
01/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/26/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
01/26/2004 ROBERT SHERRY WATER REVIEW Approved
01/26/2004 DAN CASTRO ZONING REVIEW Approved
01/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/26/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/27/2004 GERRY KOZIOL WWM REVIEW Approved
01/28/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00309 DENIED 1/26/04
1. WH is 2 KW on Sheet P-1, but 4500 W on CKT A-15,17. Please clarify.
2. On the power plan there is a receptacle on CKT A-28, but not on the Panel Schedule. Please clarify.
3. CKT A-27 shall beo counted as no less than 1200VA for the sign per NEC 220-2 (6).
4. Reference Note 5, there is no such NEC TAble as 250-95. The correct TAble is 250-22.
5. Show the X-Ray Generator on the plans, and it's proper installation per NEC 517 E.
6. Add the following note, as appropriate: "All work in patient care areas shall be performed in accordance with NEC 517-13.
7. Show fault calculations, and AFC at Panel B.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2004 LISA LESNY OUT TO CUSTOMER Completed