Permit Number: T04CM00308
Parcel: 11712043A

Address:
38 N CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00308
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Reconcile the quantities of plumbing fixtures shown in the Plumbing Fixture Schedule with the number of fixtures and type of fixtures shown on the plans. (e.g. P3, P4, FS1, FS2, FD3, and FD4). Reference Section 103.2.3, UPC 1994.
2. Revise the water pressure calculations for each meter to correspond to the actual number of fixtures being served, the total lift for each system (e.g. 31-feet for Congress St.), and the developed length for each system. Revise the pipe sizing as required. Reference Section 610.1, UPC 1994.
3. Show vent for grease trap on riser diagram 1/P2.3 (this is not the vent for the directly connected compartments of the 3-compartment sink). Reference Section 103.2.3, UPC 1994.
4. Show that the gas train for the emergency generator complies with the requirements of NFPA 37. Reference Section 915.2, IMC 2000.
5. Relocate FS1 located in alcove of room 017 to be readily accessible for cleaning and inspection. Reference Section 804.1, UPC 1994.
01/28/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The ventilation rate for rooms 201 and 202 is more appropriately identified as "Theater - Lobby" with an occupant load of 150 people per 1000 square feet and 20 CFM per person. Reference Section 403.3, IMC 2000.
2. Show how the overflow drains on the fan coil units (Note 3, Fan Coil Schedule, M3.0) are to be routed and terminated. Reference Section 307.2.3, IMC 2000.
02/12/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS UNDER T03CM05695.
02/24/2004 GERRY KOZIOL WWM REVIEW Denied Needs WW design review of basement lift station. Robert Buecher - Pioneer Bldg, 4th Floor, 100 N. Stone 617-8206

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
02/25/2004 ANGIE SHOFFSTALL REJECT SHELF Completed