Permit Number: T04CM00294
Parcel: 125110430

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T04CM00294
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2004 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Show and label the MS&R right of way line for Speedway Boulevard. The required street landscape border is to be located based on the MS&R right of way. LUC 3.7.2.4.A.1

2) A six foot high masonry screen wall is required along the southern property line adjacent to R zoned property. LUC Table 3.7.2-I The site plan includes only a 60" high wall, revise as necessary.
03/15/2004 Paul Machado ENGINEERING REVIEW Denied To: Bruce Patton, P.E.
Rick Engineering Company, Inc.
1745 E. River Road, Suite 101
Tucson, Arizona 85718
SUBJECT: Eckerd Drug Store
Site Plan T04CM00294 (Second Review)
T14S, R14E, Section 09

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies with resubmittal.
2. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. The intersection of Alvernon Way and Speedway Blvd. is subject to intersection widening per the MS&R. Per our conversation, a letter from COT transportation was to be submitted confirming that the right-of-way is at its ultimate configuration presently. This letter was not submitted. Please re-submit with the letter.
3. Acquisition of the right-of way on first Street was also to be done prior to this submittal. What is the status of acquisition? Please submit documentation with next submittal.

Drainage Report:
1. The drainage report is accepted for Site plan purposes only.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
03/16/2004 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Your response has been acknowledged. Prior to site plan approval please submit a signed and notarized copy of the Lot Combination Covenant (covenant does not have to be recorded at this time). A hold on the building's CofO will be issued until a copy of the recorded covenant and Assessors tax combination form is submitted to the Zoning Review Section for DSD records.
Previous comment: Per Pima County Assessors Records, the site is comprised of separate parcels which must be combined by providing a copy of the recorded City of Tucson Lot Combination Covenant and a copy of the approved Pima County Assessors Tax Combination form. A copy of the City of Tucson Lot Combination Covenant is attached to the yellow site plan card. The Pima County Assessors Tax Combination Form may be obtained at the Assessors office. (D.S. 2-02.2.1.A.2)

2. Per D.S. 3-05.2.1.C.2.4, the minimum height clearance for the drive through canopy is 15 feet. (D.S. 2-02.2.1.A.6)

3. Your response has been acknowledged. Cross access agreement to be submitted.
Previous comment to be addressed: A vehicular cross access agreement is required with the adjacent properties to the east and west. A copy of the recorded cross access agreement must be provided and the docket and page noted on the drawing prior to site plan approval. (D.S. 2-02.2.1.A.11)

4. Per your response, a copy of the last approved site plan was not found in the resubmittal package.
Previous comment to be addressed: Provide a copy of the last approved site plan for the McDonald's property to verify that sufficient vehicle parking will be provided as a result of the new driveway openings taking out (8) existing vehicle parking spaces.
5. Please contact Patricia Gehlen at 791-5608 ext. 1179 to discuss the feasability for a Development Standard Modification Request (DSMR) to eliminate the sidewalk required to the 1st Street right-of-way.
Previous comment: D.S. 2-08.4.1.A requires that at least one (1) sidewalk be provided to a project from each street on which the project has frontage. Provide a sidewalk to 1st Street right-of-way. (D.S. 2-02.2.1.A.12)

6. The building permit may not be issued until the "15-foot unspecified easement" located within the proposed building site is abandoned and recordation information provided to the Zoning Review Section.
Previous comment: Easements to be abandoned by separate instrument must be recorded and the docket and page noted on the plan prior to site plan approval. (D.S. 2-02.2.1.A.20)

7. All requested changes must be made to the site and landscape plans. (D.S. 2-07.2.1.A)


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
03/16/2004 DAN CASTRO HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2004 LISA LESNY OUT TO CUSTOMER Completed
03/16/2004 SUE REEVES REJECT SHELF Completed