Permit Number: T04CM00293
Parcel: Unknown

Address:
5901 S FIESTA AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM00293
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
02/05/2004 JIM EGAN FIRE REVIEW Approved
02/10/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Please provide plans sealed by a Registrant in the State of Arizona.
2. Provide Panel and Circuit number for all new loads.
3. Show location of Panel from which new circuits are to be derived.
4. Show Panel Schedule.
5. Specify conductor and conductor size.
6. Specify proper grounding per NEC Article 250.
02/19/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
02/20/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2004 LISA LESNY OUT TO CUSTOMER Completed
02/20/2004 ANGIE SHOFFSTALL REJECT SHELF Completed