Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM00283
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/11/2004 | David Witt | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T04CM000283 6/14/04 2145 N. FREMONT AVE. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SECTIONS - DETAILS - MISC. NOTES: 1. EXPANSION BOLTS / A-1 ; THE VALUES CITED CONFLICT WITH THE LISTED VALUES IN ICBO #1372. PROVIDE DEPTH OF EMBEDMENT AND COMPRESSIVE STRENGTH OF THE CONCRETE FOR THE CITED VALUES. 2. PROVIDE A CROSS SECTION OF A TYPICAL INTERIOR WALL. PLUMBING PLANS: 1. C, PLUMBING ISOMETRIC / A-2 ; THE HOT IS REQUIRED TO BE ON THE LEFT. SEE UPC 601.2 . 2. JUSTIFY THE EXISTING WATER DISTRIBUTION SYSTEM'S ABILITY TO SUPPLY BOTH EXISTING AND PROPOSED LOADS. 3. THE PRESSURE CALCULATIONS MENTIONS A 1-1/4"WATER LINE FROM THE WATER METER BUT THE SITE PLAN DIFFERS. PLEASE CLARIFY. 4. THE PLUMBING FIXTURE TABLE LISTS 2 HOSE BIBS BUT I FOUND ONLY ONE ON THE PLAN. PLEASE CLARIFY. ONLY 3 f.u. ARE LISTED FOR THE HOSE BIBS. IF THERE ARE TWO, PLEASE CORRECT THE MATH AND CHECK THE SIZES OF THE WATER DISTRIBUTION SYSTEM. MECHANICAL PLANS: 1. SHOULD THE DETAIL REFERENCE BE D / A-3 FOR THE RETURN AIR? ELECTRICAL PLANS: 1. DO THEY MAKE A 25 AMP BREAKER FOR CIRCUIT 17, 19? IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/15/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 06/15/2004 | SUE REEVES | REJECT SHELF | Completed |