Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00277
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/23/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
01/23/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
03/02/2004 | LINDA BUCZYNSKI | BUILDING-COMMERCIAL | REVIEW | Approved | T04CM00277 DENIED 1/27/04 1. Plans lack sufficient information for review, such as identification of panel and circuit number for new equipment, panel schedules, and load calculations. 2. See the attached sheet for a full description of Electrical Permit Requirements. |
03/02/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 3/02/04 T04CM00277 Load calculations do not print out clearly, but appear to be 115A for the new panel, and 901A for the service, within acceptable range. Please clarify on plans. |
03/12/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/12/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
03/12/2004 | EGRANT1 | WWM | REVIEW | Passed | |
03/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/12/2004 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/12/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |