Permit Number: T04CM00277
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00277
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2004 JIM TATE ENGINEERING REVIEW Approved
01/23/2004 DAN CASTRO ZONING REVIEW Approved
03/02/2004 LINDA BUCZYNSKI BUILDING-COMMERCIAL REVIEW Approved T04CM00277 DENIED 1/27/04
1. Plans lack sufficient information for review, such as identification of panel and circuit number for new equipment, panel schedules, and load calculations.
2. See the attached sheet for a full description of Electrical Permit Requirements.
03/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 3/02/04 T04CM00277
Load calculations do not print out clearly, but appear to be 115A for the new panel, and 901A for the service, within acceptable range. Please clarify on plans.
03/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/12/2004 JIM EGAN FIRE REVIEW Approved
03/12/2004 EGRANT1 WWM REVIEW Passed
03/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/12/2004 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2004 EGRANT1 OUT TO CUSTOMER Completed