Permit Number: T04CM00262
Parcel: 13728038B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00262
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM00262 .. 926 W VIRGINIA ST .. DGL .. 6/18/04 ..
.. 3RD Review .. (Prior comments .. dated 4/23/04)
S1. See prior comment # S3. Provide revision. Address fire rating of exterior walls per IBC Sec 6, Table #601 and #602, show on drawings , ref IBC Sec #704.11.
S2. See prior comment #S9. Provide revision. Show new exit gate and new door comply with IBC Sec #10, 11 and ANSI A117.1-98ed. Clarify / Explain how door and gate conforms.
S3. See prior comment #S15. Provide revision. Fully specify and design anchor bolts per IBC Sec 16,19, and 23, see Sec 2308.4, 2304.9, 2304.9.5, and 1913 , ref detail 3/5.
S4. See prior comment # S16. Provide revision. Detail hold-downs on drawing #5, ref schedule on drawing #5 and structural calculations, pg 6.
S5. Extend toedown across gate opening , ref Foundation Plan drawing #3.

Questions? Call Douglas Laakso, COT/DSD Structural Plans Examiner, at (520) 791 5550 x 1111.
06/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/30/2004 David Rivera ZONING REVIEW Denied DSD TRANSMITTAL

FROM: David Rivera Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T04CM00262
926 W. Virginia Street
Residential Care Services
Site Plan

Transmittal date: 2nd Review June 30, 2004

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This plan has not been approved per the Special Exception Process and therefore until we have resolution from the Zoning Examiner this plan cannot be reviewed or approved by the Zoning Review Section. It is my understanding that the Special Exception is to go to the Zoning Examiner on August 5th. No permits may be issued or any form of construction can occur on this site. Please do not request approval by the Zoning Review Section of the proposed expansion because we will not approve any permit related to the expansion on this site until the Special Exception process has been resolved and we have direction as how to proceed.

You may at your own risk, continue to submit the plans for review by other review agencies. Keep in mind that any conditions that may be imposed on this site that may alter the site or building must be incorporated in the plans and any approvals by the other reviewing agencies may have to re-review and re-approve the plans as a result of the conditions.

The Zoning Section will not review this further until the Special Exception Process has finaled.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.