Permit Number: T04CM00262
Parcel: 13728038B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00262
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2004 JIM EGAN FIRE REVIEW Denied Needs correct occupancy classification:
R-3--5 or less occupants.
R-4--More than 5 but less than 16 occupants. Fire sprinklers required if more than 8 occupants.
(See 2000 IBC Sec. 308.2 and Sec. 310.)
02/25/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied Show that the existing gas piping has the capacity to supply the requirements of the new furnace as well as any existing requirements. Reference Section 103.2.3, UPC 1994.
02/25/2004 ROBERT SHERRY WATER REVIEW Passed
02/25/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code analysis of addition. Reference Section 101.4.2.1, IECC 1998.
2. Show material, size, and slope of new condensate drain. Reference Section 307.2.2, IMC 2000.
03/09/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM00262 .. 926 W VIRGINIA ST .. DGL .. 3/12/04 ..
S1. Indicate number of occupants on drawings.
S2. Indicate code analysis on drawings.
S3. Clarify occupancies in this building :
1. Residence - R3,R4.
2. Office and Counseling - B
3. Address occupancy separation, B to R3/R4 = two hours, Table 302.3.3.
S4. Detail occupancy separation on drawings for two-hour fire-rated separation.
S5. Address fire rating of exterior walls per IBC Sec 6, Table #601 and #602, show on drawings.
S6. Detail fire-rated assembly per IBC Sec 7, including openings.
S7. Clarify fire protection requirements per IBC Sec 9.
S8. Clarify landings at five doors/doorways, to show compliance provide 'spot' elevations of finish grades, Per IBC Sec 1003.3.1, ref dwg #1,2 and 3.
S9. Clarify door spacing, per IBC Sec 1003.3.1.7.
S10.Show exit gate and new door requirements per IBC Sec #10 and 11, including ANSI A117.1-1998 ed.
S11. Show new exit gate and new door comply with IBC Sec #10, 11 and ANSI A117.1-98ed.
S12. Identify accessibile sleeping room and associated toioet and bathing facilities per IBC Sec 1107.5.
S13. Provide flashing at details #4 and 5 on drawing #5, per IBC Sec 1507.
S14. Fully detail skylight shown on drawing #3, per IBC Sec 2405 and 2606.
S15. Clarify extent of plywood on walls, ref detail #1,2,3,and 6 on drawing #5.
S16. Clarify seal (weather-resistance) at detail 2/5.
S17. Fully specify Ramset and show required edge distance is complied with, ref 3/5.
S18. Locate and detail on drawings hold-downs, ref schedule on drawing #5 and structural calculations, pg 6.
S19 Special inspection required for:
1. Epoxy anchors
2. Expansion anchors.
Questions? Call Douglas Laakso, COT/DSD Structural Plans Examiner, at (520) 791 5550 x 1111.
03/15/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved
03/17/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
03/22/2004 GERRY KOZIOL WWM REVIEW Passed
03/22/2004 DAVID RIVERA ZONING REVIEW Denied This plan has been denied at this time pending further review by the Zoning Admistrator and whether a Special Exception review and approval is required. Tom Gordon of Pima County Facilities Management has been directed to speak to Walter Tellez regarding this site and the proposed expansion. Until further notice this plan will not be reviewed by the Zoning section pending final decision. For questions please contact David Rivera with the Zoning Review Section at 791-5608 ext 1181.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
03/23/2004 SUE REEVES REJECT SHELF Completed