Permit Number: T04CM00260
Parcel: 14025006A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM00260
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2004 ROBERT SHERRY WATER REVIEW Approved
11/03/2004 Jim Egan FIRE REVIEW Denied 1. Construction of egress balconies must conform to 2003 IBC Sec. 1013 for fire rating of walls and opening proectives.
2. Additional(or relocated) stairways required per 2003 IBC Sec. 1018.2 and Table 1018.2.
3. Provide fire sprinkler system design criteria on plans.
11/10/2004 DOUG WILLIAMS ENGINEERING REVIEW Denied Each building plan set must contain a copy of the stamped/approved site plan.
11/10/2004 Gerry Koziol WWM REVIEW Denied need to review location of connection to public sewer
11/18/2004 Peter McLaughlin ZONING REVIEW Denied Provide a copy of the stamped approved site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
11/29/2004 SUE REEVES REJECT SHELF Completed