Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T04CM00260
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/03/2004 | Jim Egan | FIRE | REVIEW | Denied | 1. Construction of egress balconies must conform to 2003 IBC Sec. 1013 for fire rating of walls and opening proectives. 2. Additional(or relocated) stairways required per 2003 IBC Sec. 1018.2 and Table 1018.2. 3. Provide fire sprinkler system design criteria on plans. |
| 11/10/2004 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | Each building plan set must contain a copy of the stamped/approved site plan. |
| 11/10/2004 | Gerry Koziol | WWM | REVIEW | Denied | need to review location of connection to public sewer |
| 11/18/2004 | Peter McLaughlin | ZONING | REVIEW | Denied | Provide a copy of the stamped approved site plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/29/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 11/29/2004 | SUE REEVES | REJECT SHELF | Completed |