Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2004 JIM EGAN FIRE REVIEW Approved
01/21/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
01/21/2004 LOREN MAKUS ENGINEERING REVIEW Approved
01/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00252 DENIED 1/22/04
1. Panels H1 and L1 have main breakers according to their panel schedules, but are MLO on the SL Diagram. Please clarify.
2. The #6 GEC and EGC for the transformer should be #4, per Table 250-66 and Footnote #1.
3. Wireway indicated at 120/208 is on the 480 side of the X'FMR. Please correct to 480.
01/22/2004 ROBERT SHERRY WATER REVIEW Approved
01/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation to space. Reference Section 401 IMC 2000.
01/23/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
02/02/2004 GERRY KOZIOL WWM REVIEW Passed