Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00252
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/21/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 01/21/2004 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 01/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/22/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM00252 DENIED 1/22/04 1. Panels H1 and L1 have main breakers according to their panel schedules, but are MLO on the SL Diagram. Please clarify. 2. The #6 GEC and EGC for the transformer should be #4, per Table 250-66 and Footnote #1. 3. Wireway indicated at 120/208 is on the 480 side of the X'FMR. Please correct to 480. |
| 01/22/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation to space. Reference Section 401 IMC 2000. |
| 01/23/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/02/2004 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/02/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |