Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00233
Parcel: 11445262J

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00233
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00233 DENIED 1/22/04
1. Phase C is still overloaded. See comments 01/21/04.
2. Provide overcurrent protection for the feeder to the new panel, and size per NEC, or demonstrate that the existing OCPD is sufficient.