Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM00233 DENIED 1/22/04 1. Phase C is still overloaded. See comments 01/21/04. 2. Provide overcurrent protection for the feeder to the new panel, and size per NEC, or demonstrate that the existing OCPD is sufficient. |