Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00233
Parcel: 11445262J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00233
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
01/20/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
01/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/21/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
01/21/2004 ROBERT SHERRY WATER REVIEW Approved
01/21/2004 JIM EGAN FIRE REVIEW Approved
01/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/21/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00233 DENIED 1/21/04
1. Ckt 1 on panel schedule indicates bath and hall lights. Bath and hall lights on plan are Ckts 5 and 3. Please clarify.
2. Ckt 3 is a space on panel schedule. On plan there are lights on Ckt 3. Please clarify.
3. Lights in the hall are not on a circuit.
4. Provide a maintenance receptacle for the new AC, per NEC 210-63.
5. Ckts 18 and 20 should have the same load. Please correct.
6. With 5 receptacles on Ckt 9, load should be no less than 900 VA per NEC 220-2 (b) (9).
7. With 5 receptacles on Ckt 7, load should be no less than 900 VA per NEC 220-2 (b) (9).
8. Phase C is overloaded. My check totals 22,840 VA of connected load, 22,680 VA demand load, and over 200A. Please correct.
9. Provide overcurrent protection for the feeder to the new panel, and size per NEC, or demonstrate that the existing OCPD is sufficient.
10. Show fault calculations, and demonstrate that AFC rating at new equipment is sufficient.
01/22/2004 GERRY KOZIOL WWM REVIEW Approved