Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00224
Parcel: 106070380

Address:
1010 W LIND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00224
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2004 CRAIG GROSS ZONING REVIEW Approved
01/20/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/20/2004 LLESNY1 WWM REVIEW Passed
01/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/20/2004 ROBERT SHERRY WATER REVIEW Approved
01/21/2004 JIM EGAN FIRE REVIEW Approved
01/21/2004 JIM TATE ENGINEERING REVIEW Approved
02/09/2004 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved CITY OF TUCSON DEVELOPMENT SERVICES
ELECTRICAL REVIEW COMMENTS

DATE: January 20, 2004
ACTIVITY NUMBER: T04CM00224
PROJECT NAME: Diamonds Back / Jacobs Park Ball Field Lighting
PROJECT ADDRESS: 1010 W. Lind St.
PROJECT REVIEWER: Randy Schuler, P.E.
PHONE: (520) 791-5550 X1104

E200
1) It appears there needs to be 20 feet of #10 wire from the breakers to the line side of the lighting contactors in order to reduce the fault current to a value less than 10, 000 amps. Please specify the contactor withstand ratings.
2) Remove the equipment ground from the service lateral serving the electrical service. In addition, the 1" conduit for the (4) 500 kcmil is too small.
3) 1999 450-3b mandates the primary overcurrent protection for the 6 kva transformer cannot exceed 15 amps. In addition, the secondary overcurrent protection (the panel main breaker) cannot exceed 25 amps.
E300
1) Pole B detail is actually a 7 fixture array. Please do not adjust the loads in the panel as they approximate a 7 fixture array after power factor and +25% for continuous duty is factored in.
2) Provide minimum length of the feeders serving the existing rest room and basketball courts to insure that the fault current at the load end of the feeders is less than the withstand rating of the equipment they serve.
3) It appear the scoreboard/lighting control design is incorrect.
02/23/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved