| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | DENIED T04CM00214 2/10/04 1. New disconnect not grouped with the others per NEC 230-72. 2. Sheet E1, if this is to consist of a Revision to the approved drawings, indicate so on the plans, even if it refers to the entire sheet, and date the Revision. 3. On Sheet E1.1, Registrant shall sign and date seal. 4. 2. Sheet 2, if this is to consist of a Revision to the approved drawings, indicate so on the plans, even if it refers to the entire sheet, and date the Revision. Registrant shall sign and date seal. 5. Clarify the wording Panel A by others and under separate permit. It was understood that the current Revision was driven by the fact that such panel was thought to be existing when in fact it was not, such that it needed to be shown as new on the currently permitted plans. 6. The #6 CU from the gutter to the new meter should be sized per NEC Table 250-66, and should be #2, not #6. 7. The other #6 GND from the new disconnect to the ground bus appears to be redundant. 8. There are 2 gutter #1s on the line diagram, and Plan View and Load Calculations refer to a Gutter #1 and a Gutter #2. Please clarify. 9. Load calculations refer to a STE 185. None on SLD. |