Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00214
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
01/20/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show route, size and termination of T&P relief piping. 2. Show installation details for the water heater (valves, T&P relief, and expansion tank). 3. If the pedicures are not equipped with integral backflow preventers or air gaps, provide backflow protection for both hot and cold water supplies. 4. Provide traps for indirect waste lines from pedicures (over 5 feet). 5. Revise fixture unit calculations. |
01/20/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/20/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/20/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for beauty shop per Section 403.3, IMC 2000. |
01/22/2004 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
01/22/2004 | CAGUILA1 | WWM | REVIEW | Needs Review | |
01/22/2004 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |