Permit Number: T04CM00214
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00214
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2004 JIM EGAN FIRE REVIEW Approved
01/20/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show route, size and termination of T&P relief piping.
2. Show installation details for the water heater (valves, T&P relief, and expansion tank).
3. If the pedicures are not equipped with integral backflow preventers or air gaps, provide backflow protection for both hot and cold water supplies.
4. Provide traps for indirect waste lines from pedicures (over 5 feet).
5. Revise fixture unit calculations.
01/20/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/20/2004 ROBERT SHERRY WATER REVIEW Approved
01/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for beauty shop per Section 403.3, IMC 2000.
01/22/2004 CAGUILA1 ZONING REVIEW Needs Review
01/22/2004 CAGUILA1 WWM REVIEW Needs Review
01/22/2004 CAGUILA1 ENGINEERING REVIEW Needs Review