Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T04CM00192
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Irrigation controller was on originally permitted plans, Ckt 31, but not on revised set. No annotation of this on Revision. Please clarify. 2. Since the fused disconnect is being removed from the project, please change the 20A CB to a 15A CB for all Pumps, for overload protection, or justify otherwise. 3. City of Tucson does not allow "let Through" currents as a means of attenuating fault current . Provide fault calculations sufficient to demonstrate that Panel A is of sufficient rating. 4. Electrical Service Riser Diagram makes reference to Site Plan. Please provide such plan for Electrical Review reference. 5. Either provide disconnects for the Air Machine on Ckt 32 and the Vacuum on Keynote 5, or demonstrate otherwise that such equipment is in compliance with NEC 430 Part IX. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/10/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 02/10/2005 | SUE REEVES | REJECT SHELF | Completed |