Permit Number: T04CM00192
Parcel: 12315070A

Address:
1525 N PARK AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T04CM00192
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2004 EROSE1 WWM REVIEW Needs Review
02/02/2004 EROSE1 ENGINEERING REVIEW Needs Review
02/02/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet G.1
1. Please add the 1999 National Electrical Code and 2000 IFC to the applicable codes list.

2. Include epoxy / adhesive anchors and structural masonry to the special inspections block.

Sheet C.2
1. The screen walls at the north buffer yard are noted as having a height of 2'-6" and also 5'-0". Please resolve discrepancy and coordinate to the appropriate masonry wall detail.

Sheet A.1
1. Clarify where keynotes 9, 11 and 12 occur on the plan.


2. Please show the locations of equipment items N and P.

Sheet A.2
1. Clarify where keynotes 4, 5, 8, 9, 12 and 14 occur on the plan.

STRUCTURAL COMMENTS
Sheet S.1
1. In the special structural inspections notes, please clarify if the structural masonry inspection intent is to provide level I inspection. Ref. IBC 1704.5.1.

PLUMBING COMMENTS
Sheet P.1
1. Specify combustion air provisions for the water heater. Ref. UPC 507.

2. Indicate the total developed length of gas distribution. Ref. UPC 1217.

3. Verify requirements of Pima County wastewater management. An IWC application may be required.

ELECTRICAL COMMENTS
Sheet E.1
1. Circuit A-31 shown in the panel schedule as a spare appears to provide power to the irrigation controller. Please clarify.

2. Circuits 23 and 30 were not found. Please clarify.
02/02/2004 ELAINE ROSE ZONING REVIEW Needs Review
02/02/2004 EROSE1 WATER REVIEW Needs Review
02/02/2004 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2004 ELAINE ROSE OUT TO CUSTOMER Completed