Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00148
Parcel: 133243700

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00148
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2004 JIM TATE ENGINEERING REVIEW Approved
01/21/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
01/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00148 DENIED 1/22/04
1. Provide TEP AFC, fault calculations, and rating of new panel.
1. Load calculation for high phase is actually 79 amps, which is OK for 100A panel. Please correct from 125.8.
01/22/2004 ROBERT SHERRY WATER REVIEW Approved
01/22/2004 JIM EGAN FIRE REVIEW Approved
01/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/23/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
01/28/2004 CAGUILA1 WWM REVIEW Needs Review