Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00146
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
01/28/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
01/28/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM00146 DENIED 1/28/03 2. Sheet M1 calls for one existing A/C unit, named "AC". New AC2 has not been specified. Please do so, so that this equipment may be evaluated for electrical. 3. Lighting is indicated on Circuits, 9, 2, 4 & 6. Panel not specified. No such panel with lighting circuits 9, 4, or 6. 4. This has been an incomplete review, performed only up to the branch circuit level for power. Lighting, feeders, service, etc shall be performed after the above conditions have been clarified/corrected. |
01/28/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
01/29/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
01/29/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/29/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |