Permit Number: T04CM00146
Parcel: 133552300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00146
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00146 DENIED 1/14/03
1. Specifications call for THIN conductor. No such insulation type.
2. Ckt 30,32 is incorrectly sized at #12, since it is protected by a 30A CB. See NEC 240-3 (d).
3. Sheet M1 calls for one existing A/C unit, named "AC". Sheet E1 calls for AC and AC#2, neither of which has been designated as either new or existing on this sheet. Clarify which is which, and provide electrical requirements for the new AC, not just the existing.
4. Equipment E5 on Sheet A3 is 230V. Powered by 208V on Sheet E1. Please clarify/correct.
5. Equipment E11 on Sheet A3 is 220V. Powered by 208V on Sheet E1. Please clarify/correct.
6. Equipment E6 is 3-phase on Sheet A3. Powered single phase on Sheet E1. Please clarify/correct.
7. Equipment E12 is 20A on Sheet A3. (20) (120) = 2400 >1800 on Ckt 25. Please re-evaluate.
8. Lighting is indicated on Circuits, 9, 2, 4 & 6. Panel not specified. No such panel with these lighting circuits.
8. This has been an incomplete review, performed only up to the branch circuit level for power. Lighting, feeders, service, etc shall be performed after the above conditions have been clarified/corrected.
01/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/14/2004 ROBERT SHERRY WATER REVIEW Approved
01/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/28/2004 TACHONG1 FIRE REVIEW Needs Review
01/28/2004 TACHONG1 WWM REVIEW Needs Review
01/28/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
01/28/2004 TACHONG1 ZONING REVIEW Needs Review
01/28/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2004 TAMI ACHONG OUT TO CUSTOMER Completed