Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00130
Parcel: 121060070

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00130
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2004 JIM EGAN FIRE REVIEW Approved
01/13/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Size water supply piping using Table 6-4. Reference Sections 610.4 and 610.10, UPC 1994.
2. Revise the location of the cleanout for P2 to assure air circulation in the vent system.
3. Include the future sink in the water calculations. Reference Section 610.1, UPC 1994.
4. Provide a detail to show that the existing water heater is being repiped to current code requirements.
01/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/13/2004 ROBERT SHERRY WATER REVIEW Approved
01/13/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
01/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for expanded restroom per Section 403.3, IMC 2000.
01/14/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/22/2004 TACHONG1 WWM REVIEW Needs Review
01/22/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2004 TAMI ACHONG OUT TO CUSTOMER Completed