Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00130
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/13/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Size water supply piping using Table 6-4. Reference Sections 610.4 and 610.10, UPC 1994. 2. Revise the location of the cleanout for P2 to assure air circulation in the vent system. 3. Include the future sink in the water calculations. Reference Section 610.1, UPC 1994. 4. Provide a detail to show that the existing water heater is being repiped to current code requirements. |
| 01/13/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/13/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/13/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 01/13/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for expanded restroom per Section 403.3, IMC 2000. |
| 01/14/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/22/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 01/22/2004 | TACHONG1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |