Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM00109
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Show the cleanouts added in revision 1 on the waste and vent isometric to coordinate with the plumbing plans. 2. Correct the arithmetic on the water pressure calculations. Reference Section 608.1, UPC 1994. 3. Comment not addressed. Provide calculations to show that the sizes of the water heater flue connectors are sized per the requirements of the manufacturer's listing. Reference Section 103.2.3, UPC 1994. 4. Comment not addressed. Revise the combustion air openings for the water heaters to comply with the requirements of Section 507, UPC 1994 as amended by the State of Arizona. 5. Provide the specifications for WH-2. Reference Section 103.2.3, UPC 1994. 6. Provide insulation on the circulating hot water piping per Section 804.5, IECC 2000. 7. Provide calculations to support the size of the expansion tank serving WH-1 and the storage tank. Reference Section 608.3, UPC 1994 with AZ State amendments. |
| 09/22/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. The revision of the hobby shop and apartment to R-3 occupancy along with the garage door for the hobby shop makes the supply and return ductwork from HP-7 and HP-8 that enters the hobby shop in violation of Section 309.1.1, IRC 2000. 2. Comment not addressed. Provide exhaust for the clothes dryer on the second floor. Reference Section 504, IMC 2000. 3. Comment not addressed. The backflow device (Watts 9D) provided to protect the potable water system from the radiant slab heating system is not suitable for a pressurized, closed system. Provide a reduced pressure backflow preventer. Reference Section 603.0, UPC 1994. 4. Revise the font used on sheet M3 to be legible. Reference Section 302.3, Uniform Administrative Code, 1997 |
| 09/27/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. It is accepted that the Phase Perfect DPC-30 on Keynote 3 of Sheet E1 is rated for the diversity of the anticipated load on Panel WS. Please correct the 75 KVA Transformer on the One Line Diagram to be replaced the DPC-30, since this is the intent. 2. Remove Transformer from Owner's Panel, because Panel WS is to be powered from the DPC-30 per the comment above. 3. Specify that any boxes, fittings, and disconnect enclosures installed in the Class II, Division 2 area be dusttight. For the motors and lighting fixtures, the note on the plans requiring the Contractor to submit cut sheets for the lighting fixtures and motors, is acceptable, and the Plans Examiner will add a Notice to such Inspectors to that effect. 4. Applicant shall go to Pima County Addressing to obtain addresses for all new/relocated meters. Take such addresses to DSD Permit Clerks for data entry into the City permitting system. Addresses for all new meters as shown on the plans shall correspond to those in City/County database. 5. Provide power for DC-1. See Sheet M1. Coordinate with Mechanical and clarify. |
| 10/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/17/2005 | DAVID RIVERA | ZONING | REVIEW | Denied | 10/17/05 Development Services Department Zoning Review Section David Rivera Principal Planner Comments: 1. The building plans cannot be approved at this time. Approval of the site plan or DDO approval for the proposed building setbacks specifically the balcony along the north side of the buillding. |
| 10/24/2005 | DAVE MANN | BUILDING-COMMERCIAL | REVIEW | Denied | Sheet C-2 Provide truncated dome detectable warnings at ramps that meet ANSI A117.1-2003 Sections 406.13 and 705. Sheet G-1.0 Provide grab bar blocking and other dimentions that meet ANSI A117.1-2003 Sections 604 and 804. Sheet S2 Shop drawing for stairs are to be reviewed by the Engineer of Record and reviewed by the City before installation. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/14/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 11/14/2005 | SUE REEVES | REJECT SHELF | Completed |