Permit Number: T04CM00109
Parcel: 11105197A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00109
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show the cleanouts added in revision 1 on the waste and vent isometric to coordinate with the plumbing plans.
2. Correct the arithmetic on the water pressure calculations. Reference Section 608.1, UPC 1994.
3. Comment not addressed. Provide calculations to show that the sizes of the water heater flue connectors are sized per the requirements of the manufacturer's listing. Reference Section 103.2.3, UPC 1994.
4. Comment not addressed. Revise the combustion air openings for the water heaters to comply with the requirements of Section 507, UPC 1994 as amended by the State of Arizona.
5. Provide the specifications for WH-2. Reference Section 103.2.3, UPC 1994.
6. Provide insulation on the circulating hot water piping per Section 804.5, IECC 2000.
7. Provide calculations to support the size of the expansion tank serving WH-1 and the storage tank. Reference Section 608.3, UPC 1994 with AZ State amendments.
09/22/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. The revision of the hobby shop and apartment to R-3 occupancy along with the garage door for the hobby shop makes the supply and return ductwork from HP-7 and HP-8 that enters the hobby shop in violation of Section 309.1.1, IRC 2000.
2. Comment not addressed. Provide exhaust for the clothes dryer on the second floor. Reference Section 504, IMC 2000.
3. Comment not addressed. The backflow device (Watts 9D) provided to protect the potable water system from the radiant slab heating system is not suitable for a pressurized, closed system. Provide a reduced pressure backflow preventer. Reference Section 603.0, UPC 1994.
4. Revise the font used on sheet M3 to be legible. Reference Section 302.3, Uniform Administrative Code, 1997
09/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. It is accepted that the Phase Perfect DPC-30 on Keynote 3 of Sheet E1 is rated for the diversity of the anticipated load on Panel WS. Please correct the 75 KVA Transformer on the One Line Diagram to be replaced the DPC-30, since this is the intent.
2. Remove Transformer from Owner's Panel, because Panel WS is to be powered from the DPC-30 per the comment above.
3. Specify that any boxes, fittings, and disconnect enclosures installed in the Class II, Division 2 area be dusttight. For the motors and lighting fixtures, the note on the plans requiring the Contractor to submit cut sheets for the lighting fixtures and motors, is acceptable, and the Plans Examiner will add a Notice to such Inspectors to that effect.
4. Applicant shall go to Pima County Addressing to obtain addresses for all new/relocated meters. Take such addresses to DSD Permit Clerks for data entry into the City permitting system. Addresses for all new meters as shown on the plans shall correspond to those in City/County database.
5. Provide power for DC-1. See Sheet M1. Coordinate with Mechanical and clarify.
10/11/2005 ROBERT SHERRY WATER REVIEW Approved
10/17/2005 DAVID RIVERA ZONING REVIEW Denied 10/17/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The building plans cannot be approved at this time. Approval of the site plan or DDO approval for the proposed building setbacks specifically the balcony along the north side of the buillding.
10/24/2005 DAVE MANN BUILDING-COMMERCIAL REVIEW Denied Sheet C-2
Provide truncated dome detectable warnings at ramps that meet ANSI A117.1-2003 Sections 406.13 and 705.

Sheet G-1.0
Provide grab bar blocking and other dimentions that meet ANSI A117.1-2003 Sections 604 and 804.

Sheet S2
Shop drawing for stairs are to be reviewed by the Engineer of Record and reviewed by the City before installation.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
11/14/2005 SUE REEVES REJECT SHELF Completed