Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00109
Parcel: 11105197A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00109
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the fixture unit schedule (as shown on the first set of the plans).
2. Show the cleanouts added in revision 1 on the waste and vent isometric to coordinate with the plumbing plans.
3. Correct the arithmetic on the water pressure calculations. Reference Section 608.1, UPC 1994.
4. Provide calculations to show that the sizes of the water heater flue connectors are sized per the requirements of the manufacturer's listing. Reference Section 103.2.3, UPC 1994.
5. Revise the combustion air openings for the water heaters to comply with the requirements of Section 507, UPC 1994 as amended by the State of Arizona.
07/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The revision of the hobby shop and apartment to R-3 occupancy along with the garage door for the hobby shop makes the supply and return ductwork from HP-7 and HP-8 that enters the hobby shop in violation of Section 309.1.1, IRC 2000.
2. Comment not addressed for 2nd floor. Provide exhaust for the clothes dryer on the second floor. Reference Section 504, IMC 2000.
3. The backflow device (Watts 9D) provided to protect the potable water system from the radiant slab heating system is not suitable for a pressurized, closed system. Provide a reduced pressure backflow preventer. Reference Section 603.0, UPC 1994.
07/12/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Extent of classified location has been identified. Would like to discuss the following: the presence of the Milling Machine and the Mini-Lathe, and the possibility of combustible dusts under Group E may have to be considered; lighting fixtures to be installed in this area, considering that there is no correspondence on the list of Symbols and no submittal of fixture cut sheets; City amendments to NEC 502.1.
2. The Phase Perfect DPC-30 on Keynote 3 of Sheet E1 is rated for a steady state output current of 80A at 30 HP per the website http://www.phaseperfect.com/dpc30prodinfo.htm
Clarify that this piece of equipment would not be overloaded at the calculated load of 83 amps.
3. Now that the size of Overcurrent Protection for the transformer feeder has been clarified, it shall protect the conductor at its ampacity. Size 1/0, with an ampacity of 150A, is not protected by a 200A CB.
07/15/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Approved
07/29/2004 DAVID RIVERA ZONING REVIEW Denied July 29, 2004

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments:

The Zoning Review Section has reviewed the building plans but cannot approve them until the site plan has been approved and re-stamped by all DSD reviewing agencies. Please include with the building plans two copies of the approved and stamped site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/01/2004 ANGIE SHOFFSTALL REJECT SHELF Completed