Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00109
Parcel: 11105197A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00109
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Openings in guard rails may not have openings 4"or larger. Revise detail sheet A-5. Reference section 1003.2.12.2 IBC
2. Provide letter to Dave Mann, Building Official, for approval of deferred submittal. Note: include date of proposed submittal.
3. Include 2 copies of Sheets G1.0 and G2.0
4. Provide listing for ½ hour fire assembly to be used. Note: Plans indicate ½" drywall, (not type x).
06/02/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide sufficient information to demonstrate compliance with the requirements of Chapter 5, IECC 1998 for the building envelope, mechanical systems, service water heating, and lighting.
2. Comment not addressed. Coordinate Detail 2/M1 with the First Floor Mechanical Plan/M1. Reference Section 106.3.1, IMC 2000.
3. Comment not addressed. Provide the Hobby Shop with a dust collection and exhaust system. Reference Section 510.2.1, IMC 2000.
4. Comment not addressed. Provide fire dampers for ducts from HP7 and HP8 that penetrate the walls separating the Hobby Shop from the residential areas. Reference Section 607, IMC 2000.
5. Comment not addressed. Provide exhaust for the clothes dryers. Reference Section 504, IMC 2000.
6. Comment not addressed. Provide backflow protection for the potable water system from the radiant slab heating system. Reference Section 1206.3, IMC 2000, and Section 603.0, UPC 1994.
7. Provide working clearance for the radiant slab system boiler. Reference Section 1004.3, IMC 2000. Note: Show all equipment drawn to scale.
8. Show the piping layout and installation details for the radiant slab system boiler. Provide the calculations for the sizing of the expansion tank. Reference Sections 1005 and 1009, IMC 2000.
9. Provide safety and electrical information for the radiant slab system boiler showing how the installation will comply with Sections 1006 and 1007, IMC 2000.
10. Revise the size of the lettering used on the detail of the radiant slab piping to at least 10 points. Reference Section 103.2.3, UPC 1994.
06/02/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water fixture units for the clothes washers shown in the schedule to "public use" instead of "private use" per Tables 6-3 and A-2, UPC 1994. Coordinate the number of hose bibbs in the tabulation with the number shown on the plans. Revise pipe sizes as required.
2. Coordinate the waste and vent isometric, and the CW, HW isometric with the plumbing plans.
3. Provide information to show that the specified water closet is capable of operating with a residual pressure of 8 psig or use a residual pressure of 15 psig. Reference Section 608.1, UPC 1994.
4. Show the route and sizing of the gas piping on the drawings. Reference Section 103.2.3, UPC 1994.
5. Comment not addressed. Show the route and termination of the water heater and boiler flues. Reference Section 103.2.3, UPC 1994.
6. Comment not addressed. Provide combustion air for the water heater. Reference Section 507, UPC 1994 as amended by the State of Arizona.
7. Provide terminal cleanouts for floor drain, P7 and P4 in apartments 1, 3, 4, and 7. Reference Section 707.4, UPC 1994.
8. Provide cleanouts for the second floor fixtures. Reference Section 707.4, UPC 1994, AS AMENDED BY THE STATE OF ARIZONA.
06/16/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Please identify extent of classified location per NEC 500-8. Keynote 11 may refer to such area, but the extent of that area is not defined on the plans. In the specification of compliance with Article 502, the location of seal-offs must be identified. Please coordinate with the Mechanical Engineer and Mechanical review comment #3. And note that with the presence of the Milling Machine and the Mini-Lathe, the possibility of combustible dusts under Group E may have to be considered. Please coordinate this item with the End-User to determine exact intent.
2. The Phase Perfect DPC-30 on Keynote 3 of Sheet E1 is rated for a steady state output current of 80A at 30 HP per the website http://www.phaseperfect.com/dpc30prodinfo.htm
According to this website, output voltage would be equal to single-phase input voltage, or approximately 240V. Thus the current would be transformed to 92.3A on the secondary of the transformer. It is unclear how this converter can serve 99.3 A at 35.8 KVA. The load calculations for Panel WS do not itemize separate pieces of machinery, and therefore it is not possible to determine whether such calculations invoked such Code sections as NEC 220-21 for Coincident Loads. Please clarify/correct as necessary. And please add the phase converter to the One Line Diagram.
4. Load calculations for Panel C, counting 5.8 KVA for Receptacle loads, appear to be low in this category. I count 83 receptacles not on appliance circuits, for a total of 14.9 KVA. This being the case, total would be 58.9 KVA, and total amps well over the 200A rating of the panel.
5. Please clarify the size of Overcurrent Protection for the feeder emerging from the top left of the meter pac. Understood that the meter pac has integral over-current protection, but size needs to be clarified.
6. The 400A CB at the meter pac for Panel OW, protecting a 250 MCM feeder of ampacity 255 A, is oversized.
7. The GND in the feeder to Panel OW, with a 400A CB ahead of it, shall be sized a minimum of #3, not #4.
06/18/2004 SREEVES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2004 SUE REEVES OUT TO CUSTOMER Completed