Permit Number: T04CM00109
Parcel: 11105197A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM00109
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide sufficient information to demonstrate compliance with the requirements of Chapter 5, IECC 1998 for the building envelope, mechanical systems, service water heating, and lighting.
2. Coordinate Detail 2/M1 with the First Floor Mechanical Plan/M1. Reference Section 106.3.1, IMC 2000.
3. Provide the Hobby Shop with a dust collection and exhaust system. Reference Section 510.2.1, IMC 2000.
4. Provide fire dampers for ducts from HP7 and HP8 that penetrate the walls separating the Hobby Shop from the residential areas. Reference Section 607, IMC 2000.
5. Provide exhaust for the clothes dryers. Reference Section 504, IMC 2000.
6. Clarify how the radiant floor heating system is being used in this project. Show size and routes for supply and return piping to the under-floor radiant heat manifolds. Reference Section 106.3.1, IMC 2000.
7. Provide backflow protection for the potable water system. Reference Section 1206.3, IMC 2000, and Section 603.0, UPC 1994.
8. Show how the radiant heat system can be drained down to comply with Section 1206.2, IMC 2000.
01/23/2004 ROBERT SHERRY WATER REVIEW Approved
01/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water fixture unit schedule using the values from Table 6-3, UPC 1994. Include the hose bibbs in the tabulation. Revise pipe sizes as required.
2. Show the sizes of the water meter and reduced pressure backflow preventer on the drawing.
3. Revise the water pressure calculations to include the pressure drops from the reduced pressure backflow preventer and static lift along with the required residual pressure. Correct the developed length of the piping as required to agree with the distance from the meter to the most remote outlet as shown on the drawings. Reference Section A3, UPC 1994.
4. Provide complete water, waste and vent isometrics. Reference Section 103.2.3, UPC 1994.
5. Provide shutoff valves for the water and fire protection systems in compliance with Sections 6.6.1, NFPA 13R.
6. Coordinate the gas load calculation with the specified appliances. Show the route and sizing of the gas piping on the drawings. Reference Section 103.2.3, UPC 1994.
7. Show the route and termination of the water heater flue. Reference Section 103.2.3, UPC 1994.
8. Provide combustion air for the water heater. Reference Section 507, UPC 1994 as amended by the State of Arizona.
9. Show the design for rainwater drainage of the decks located North of apartments 5 and 6. Reference Appendix D, UPC 1994.
01/30/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Stairway serving the upstairs apartments to have minimum rise and maximum run as per section 1003.3.3.3 IBC. Provide detail on plans.
2. Openings in guard rails may not have openings 4"or larger. Revise detail sheet A-5. Reference section 1003.2.12.2 IBC
3. Provide design for guard rails resisting loads per sections 1607.7.1 and 1607.7.1.1
4. Upstairs exit balcony to be designed utilizing a 100# live load. Calculations utilizing a 40# live load. Revise calculations and plans. Reference Table 1607.1 IBC.
5. Due to additional load criteria for the exit balcony, provide justification for proposed connections at wall/ledger and joist of balcony.
6. Due to the equipment proposed and use of the hobby shop shall be classified an F-1. References section 306 IBC. Revise allowable area calculations and plans to reflect compliance with the building code.
7. Please clarify that the proposed attic access is accessible to all attic areas over 30" in height. Reference section 1208 IBC.
8. Provide the required natural ventilation and light as required by sections 1202.4 and 1204.2 IBC. Revise plans
9. Provide emergency escape per section 1009 IBC in bedrooms. Revise plans. See bedrooms without windows and required sill height and openings.
10. Dwelling units that are Type B are required to comply with section 1003 A117.1 ANSI. Provide details, notes and cross sections how compliance is to be achieved. Examples: Threshold at primary entrance, show a cross section. Laundry facilities provide general note on requirements.
11. Provide calculation for openings in the required exterior firewall. Reference Table 704.8 IBC.
12. Door and window schedule to include U values that comply with the energy calculations.
13. Provide rating for the required fire door and its assembly. See door schedule
14. All ground level units are required to be accessible. References section 1107.5.4 IBC. Note: One unit has an elevator thereby exception does not apply.
02/10/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Please identify extent of classified location per NEC 500-8, and specify compliance with Article 502. Note that the Structural Plans Examiner has rejected the plans on the basis of building classification. Please coordinate with the Architect before assuming the present configuration for the layout.
2. Please show the phase converter, from which 3-phase (for the machinery) is being derived from single phase input.
3. Panel OW does not serve a dwelling unit, and as such it is not subject for the Optional Load Calculations per NEC 220-30. Note that with 25 exterior lights of indeterminate power consumption, and 10 receptacles, 0.6 KVA could not be an accurate count for lighting and receptacle loads.
4. Same as above for Panel C.
5. Identify specifically which separate branch circuit is to serve the elevator lighting, per NEC 620-22 (a). And please annotate that the disconnect on Keynote 9 shall be lockable in the open position.
6. Identify specifically which separate branch circuit is to serve the hoist pit for receptacle and lighting, per NEC 620-24 (a). Show the lighting switch, and locate per NEC 620-24 (b).
7. There is a lighting fixture in the elevator area on CKT C-5. It is not clear whether it serves the car or the pit, and in either case, it could not be on the same circuit as the lights and receptacles in the adjacent rooms. See the two comments directly above.
8. CKT C-27 feeds both the elevator receptacle and the ceiling fans in plan view, but Panel Schedule only notes the Elevator Motor on this Circuit. Please clarify.
9. Specify the type and size of Overcurrent Protection for all feeders. The One Line Diagram shows all feeders coming directly out of the meter pack.
10. Provide OCPD for the transformer per Article. Per the Line Diagram, there is no protection on the primary or the secondary.
11. Per Note 6 on Sheet E0, the HVAC units shall have RK5 fuses. On plan view it is not clear that such disconnects are to be fused, and the legend does not have a corresponding symbol.
12. Please provide a symbol on the legend for the light fixture on Circuit OW-4.
13. Circuit A14 has an exterior WP receptacle and the refrigerator in Plan View. Only the refrig. on the panel schedule. Please clarify.
14. Sanding Machine disconnect is located in a separate room from the machinery. Please correct.
02/18/2004 Patricia Gehlen ZONING REVIEW Denied Zoning
2/18/2004
Zoning will review and approve the plans once Structural has approved the building plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2004 TAMI ACHONG OUT TO CUSTOMER Completed
02/18/2004 ANGIE SHOFFSTALL REJECT SHELF Completed