Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM00109
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2006 | DAVID RIVERA | ZONING | REVIEW | Denied | David Rivera Principal Planner January 9, 2006 Zoning has reviewied the building plans but cannot approve the plans until approved by the Building reviewer. This is to ensure that the design of the building does not change and affect items such height, footprint, square footage, etc. |
| 12/06/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste and vent diagram with the plumbing plans. Add a cleanout for P-5 on the second floor. Reference Sections 103.2.3 and 707.4, UPC 1994. 2. The calculations to show that the sizes of the water heater flue connectors are sized per the requirements of the manufacturer's listing were not included with the response to the previous comments. Sheet M-1 (first floor) shows an 8" flue going up to the second floor but on sheet M-2 the 8" flue becomes a 10" flue. Also, sheet M-2 calls out a "Type E" flue; is this supposed to be a Type B flue? Reference Section 103.2.3, UPC 1994. |
| 12/06/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. The revision of the hobby shop and apartment to R-3 occupancy along with the garage door for the hobby shop makes the supply and return ductwork from HP-9 that enters the hobby shop in violation of Section 309.1.1, IRC 2000. |
| 12/09/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T04CM00109-5 .. 3622 E PRESIDIO ROAD .. RE-SUBMITTAL #5 (Dated 12/1/05) .. DGL .. 2ND REVIEW .. 12/12/05 .. S1. See prior 1st comment, detail #1 on sheet C-2 also requires truncated domes. (Sheet C-2 Provide truncated dome detectable warnings at ramps that meet ANSI A117.1-2003 Sections 406.13 and 705.) S2. See prior 2nd comment, show compliance with cited code sections. (Sheet G-1.0 Provide grab bar blocking and other dimentions that meet ANSI A117.1-2003 Sections 604 and 804.) S3. See prior 3rd comment, shop drawing stamp showing submittal requirements will be applied to approved copies of revised drawings: Stating; Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson , Development Services Department for approval prior to erection for : Stairs. (Sheet S2 Shop drawing for stairs are to be reviewed by the Engineer of Record and reviewed by the City before installation.) Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
| 12/20/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Applicant shall go to Pima County Addressing to obtain addresses for all new/relocated meters. Take such addresses to DSD Permit Clerks for data entry into the City permitting system. Addresses for all new meters as shown on the plans shall correspond to those in City/County database. 2. Power for DC-1 does not appear to include the 1/8 HP, 115/1/60 Automatic Shaker. Reference Sheet M1, Dust Collector Schedule. Also add the requirement to fuse per manufacturer specifications. |