Permit Number: T04CM00109
Parcel: 11105197A

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T04CM00109
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2006 DAVID RIVERA ZONING REVIEW Approved
12/09/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Clarify the height of screen walls on the landscape and site plans (different measurements indicated) per DS 2-07.2.2.3. Comment pending from previous review.

2. A minimum distance of two (2) feet must be maintained between a PAAL and any wall, screen, or other obstruction per DS 3-05.2.2.B.3. The Site / Utility / Grading Plan indicates a 6' wall next to the first parking space to the north, dimension space accordingly on landscape and site plans. Comment pending from previous review.

3. A 25' foot minimum height clearance, free of any overhead obstructions (wires, branches, etc.), shall be provided above the refuse collection site per DS 6-01.4.3.G. Relocate tree within refuse area as necessary.