Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00088
Parcel: 13419042C

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T04CM00088
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2004 EROSE1 WWM REVIEW Needs Review
01/27/2004 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q Sheet S1.1 indicates in the general structural notes under special inspections that special inspection for field welding is required. The special inspection certificate submitted specifically has noted that special inspection for field welding is "N/A". Please clarify. There are details on the plans which could be done in a shop but which typically are done in the field (Detail 103 for example).

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q Please provide electrical circuiting information for the "hand drawn" receptacles that were added to Sheet E2.

-End of Review-
01/27/2004 EROSE1 WATER REVIEW Needs Review
01/27/2004 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/27/2004 ELAINE ROSE OUT TO CUSTOMER Completed