Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM00085
Parcel: 124120470

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00085
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2004 RPALMA1 FIRE REVIEW Approved
01/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/09/2004 JEGAN BUILDING-COMMERCIAL REVIEW Approved
01/09/2004 ROBERT SHERRY WATER REVIEW Approved
01/09/2004 PATRICIA GEHLEN ZONING REVIEW Approved
01/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/09/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/12/2004 MELISSA POULIN WWM REVIEW Passed
01/12/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00085 DENIED 1/9/04
1. Locate AC units in plan view, along with their disconnects, and any required maintenance receptacles.
2. Specify the Overcurrent Protective Device in the disconnect to Panel B.
3. Clarify the redundancy of the wording "Panel B" on both panel schedules.