Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00085
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2004 | RPALMA1 | FIRE | REVIEW | Approved | |
| 01/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/09/2004 | JEGAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/09/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/09/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 01/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/09/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 01/12/2004 | MELISSA POULIN | WWM | REVIEW | Passed | |
| 01/12/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM00085 DENIED 1/9/04 1. Locate AC units in plan view, along with their disconnects, and any required maintenance receptacles. 2. Specify the Overcurrent Protective Device in the disconnect to Panel B. 3. Clarify the redundancy of the wording "Panel B" on both panel schedules. |