Permit Number: T04CM00084
Parcel: 126130170

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00084
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2004 JIM EGAN FIRE REVIEW Approved
01/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00084 DENIED 1/9/04

1. Please clarify wattage of WH. Is 3500W on E.1, and 3000W on MP.1.
2. If WH is 3000W, at 240V it draws 12.5A. Per NEC 422-111 (e) (2) the CB shall not exceed 20A.
3. If WH is 3500W, at 240V it draws 14.6A. Per NEC 422-111 (e) (2) the CB shall not exceed 25A, because (14.6) (1.5) = 21.9.
4. Please specify the lighting fixtures on B-3 and B-5.
01/09/2004 ROBERT SHERRY WATER REVIEW Approved
01/09/2004 PATRICIA GEHLEN ZONING REVIEW Approved
01/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/09/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/21/2004 GERRY KOZIOL WWM REVIEW Approved
04/21/2004 NOT AVAILABLE BUILDING-COMMERCIAL REVIEW Approved ;

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2004 TAMI ACHONG OUT TO CUSTOMER Completed