Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00084
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
01/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
01/09/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM00084 DENIED 1/9/04 1. Please clarify wattage of WH. Is 3500W on E.1, and 3000W on MP.1. 2. If WH is 3000W, at 240V it draws 12.5A. Per NEC 422-111 (e) (2) the CB shall not exceed 20A. 3. If WH is 3500W, at 240V it draws 14.6A. Per NEC 422-111 (e) (2) the CB shall not exceed 25A, because (14.6) (1.5) = 21.9. 4. Please specify the lighting fixtures on B-3 and B-5. |
01/09/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/09/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
01/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/09/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
04/21/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/21/2004 | NOT AVAILABLE | BUILDING-COMMERCIAL | REVIEW | Approved | ; |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/21/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |