Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00080
Parcel: 133552300

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00080
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Confirm that suspended water heaters comply with access requirements of section 511.0, UPC 1994 with AZ State amendments.
2. Show the expansion tank on the detail of the water heater installation. Reference Section 608.3, UPC 1994.
3. The water supply piping calculations provided are incomplete and do not show that the piping has been sized in accordance with Section 610.4, UPC 1994.
4. Show that the connection of the new vent to an existing 1-1/2" vent will comply with the requirements of Table 7-5, UPC 1994.
02/09/2004 GERRY KOZIOL WWM REVIEW Denied Needs "hold harmless letter" for T.I.
Public sewer not released as yet.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
02/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed