Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM00080
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/05/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Confirm that suspended water heaters comply with access requirements of section 511.0, UPC 1994 with AZ State amendments. 2. Show the expansion tank on the detail of the water heater installation. Reference Section 608.3, UPC 1994. 3. The water supply piping calculations provided are incomplete and do not show that the piping has been sized in accordance with Section 610.4, UPC 1994. 4. Show that the connection of the new vent to an existing 1-1/2" vent will comply with the requirements of Table 7-5, UPC 1994. |
02/09/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs "hold harmless letter" for T.I. Public sewer not released as yet. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/10/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
02/09/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |