Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00080
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/15/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/15/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/15/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide equipment data for water heater. Reference Section 103.2.3, UPC 1994. 2. Confirm that suspended water heater complies with the access requirements of section 511.0, UPC 1994 with AZ State amendments. 3. Provide detail of water heater installation, including excess pressure relief, expansion tank, and valves. Reference Section 103.2.3, UPC 1994. 4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Section 704.4, IECC 1998. 5. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. 6. Provide upper terminal cleanouts on horizontal drainage pipe. Reference Section 707.4, UPC 1994. 7. Show that the connection of the new vent to an existing 1-1/2" vent will comply with the requirements of Table 7-5, UPC 1994. |
| 01/15/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/21/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/26/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/27/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs holds harmless letter. Public sewer not released as yet. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/29/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 01/27/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |