| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2004 | JIM EGAN | FIRE | REVIEW | Approv-Cond | Contact Hazardous Materials Inspector (791-4502) for 704M signage. |
| 01/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct the riser diagram for water. 2. Revise water pressure calculations to show how the water piping was sized. Include existing fixtures (e.g. hose bibbs) in calculations. Provide size of the reduced pressure backflow preventer. Reference Section 610.4, UPC 1994. 3. Revise fixture unit schedule using values from Tables 6-3 and 7-3, UPC 1994. 4. Resize gas line branch to RU-1. Redraw plan to reflect actual placement of the rooftop units. 5. Correct connections of P-1 and P-4 on the riser diagram on both drawings. |
| 01/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the mechanical as required by the resolution of the corridor issue |
| 01/14/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 01/14/2004 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/14/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review |