Permit Number: T04CM00047
Parcel: 131010310

Address:
4912 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00047
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2004 JIM EGAN FIRE REVIEW Approv-Cond Contact Hazardous Materials Inspector (791-4502) for 704M signage.
01/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the riser diagram for water.
2. Revise water pressure calculations to show how the water piping was sized. Include existing fixtures (e.g. hose bibbs) in calculations. Provide size of the reduced pressure backflow preventer. Reference Section 610.4, UPC 1994.
3. Revise fixture unit schedule using values from Tables 6-3 and 7-3, UPC 1994.
4. Resize gas line branch to RU-1. Redraw plan to reflect actual placement of the rooftop units.
5. Correct connections of P-1 and P-4 on the riser diagram on both drawings.
01/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the mechanical as required by the resolution of the corridor issue
01/14/2004 LLESNY1 WWM REVIEW Needs Review
01/14/2004 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review
01/14/2004 LLESNY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2004 LISA LESNY OUT TO CUSTOMER Completed