Permit Number: T04CM00047
Parcel: 131010310

Address:
4912 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00047
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2004 JIM EGAN FIRE REVIEW Denied Provide list of all hazardous materials in retail area and storage. List quantities for each. Provide MSDS for all hazardous materials.
01/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagram for water.
2. Provide water pressure calculations to show how the water piping was sized. Include existing fixtures (e.g. hose bibbs) in calculations. Provide sizes of the water meter and reduced pressure backflow preventer.
3. Revise fixture unit schedule using values from Tables 6-3 and 7-3, UPC 1994.
4. Resize gas lines branches to the rooftop units.
5. Correct connections of P-1 and P-4 on the riser diagram.
6. Provide service sink per chapter 29, IBC 2000.
7. Show elevation of finished floor and rim elevation of upstream manhole.
01/07/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied
01/07/2004 ROBERT SHERRY WATER REVIEW Approved
01/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations per Section 403.3, IMC 2000.
2. Show air flow quantities for all diffusers.
3. Show exhaust flow rates for restrooms. (Minimum of 75 CFM per water closet or urinal)
01/09/2004 PATRICIA GEHLEN ZONING REVIEW Approved
01/09/2004 TACHONG1 WWM REVIEW Needs Review
01/09/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed