Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM00031

1/28/04 2922 E. ADAMS ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. GRADING NOTE #1 ; PLEASE CHANGE "PIMA COUNTY" TO "CITY OF TUCSON".

FOUNDATION PLANS:

1. INDICATE THE LOCATIONS AND DESCRIPTIONS OF THE HOLD-DOWNS FOR THE BRACED WALL PANELS. SEE R602.10.6 .

FLOOR PLANS:

1. PLEASE NAME THE ROOM EAST OF THE KITCHEN BASED ON IT'S USE.

2. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE .

STRUCTURAL PLANS:

1. PROVIDE A BRACED WALL PANEL AT SOME LOCATION ALONG THE NORTHERN EAST/WEST WALL TO REDUCE THE DISTANCE BETWEEN THE B.W.PANELS TO 25' MAX.

ELEVATIONS:

1. HOW IS THE RIGHT HAND PORTION OF THE ROOF DRAINED?

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A CROSS SECTION OF THE FIREPLACE FRAMING, INCLUDING THE DIMENSIONED HEARTH..

2. GENERAL STRUCTURAL NOTE #1 / S101 ; THE CODE REFERENCE SHOULD BE THE I.R.C.

3. G.S.N. #2 / S101 ; THE LIVE LOAD SHOULD BE 20 P.S.F., REDUCIBLE. THE 16 P.S.F. IS ALREADY REDUCED. SEE TABLE 301.5 .

4. G.S.N. #2 / S101; THE BASIC WIND SPEED SHOULD BE 90 M.P.H. SEE THE CITY I.R.C.REVISIONS ON OUR WEB SITE.

5. G.S.N. #2 / S101 ; SEISMIC ZONE 2A IS U.B.C. THE I.R.C. REFERS TO"SEISMIC DESIGN CATEGORY C" FOR TUCSON.

6. G.S.N.,FOUNDATION & EARTHWORK #1 ; THE 1' 6" MINIMUM DEPTH FOR FOOTING BEARING DIFERS FROM YOUR DETAILS. SEE ALSO THE NEXT NOTE #

7. 4 / S101 ; DESCRIBE THE TRANSVERSE AND VERTICAL BARS.

8. 6 / S101 ; THE EPOXY INSTALLATION REQUIRES A SPECIAL INSPECTION. THE FORMS ARE AVAILABLE AT THE PERMIT COUNTER. PLEASE ADD TO THE "SPECIAL INSPECTIONS" ON S201 .

9. 7 / S101 ; PLEASE DIMENSION THE FOOTING.

10. SHEAR WALL SCHEDULE / S201 ; PLEASE SEE R602.10 REGUARDING THE LENGTHS OF BRACED WALL PANELS, ANCHOR BOLT PLACEMENT (R602.10.6), AND HOLD DOWNS (ALSO R602.10.6).

11. 1 / S201 ; PROVIDE FIRE BLOCKS IN THE WALL AT THE CEILING LINE.

12. 2 / S201 ; SPECIFY THE JOIST HANGER.

13. 4 / S201 ; PROVIDE FIRE BLOCKS AT THE CEILING LINE.

14. 4 / S201 ; SPECIFY THE JOIST HANGER.

15. FRAMING PLAN / S201 ; R602.10 DOESN'T PROVIDE FOR A 2' BRACED WALL PANEL.AT THE NORTHEAST CORNER.

16. FRAMING PLAN / S201 ; PROVIDE AND SPEC THE HOLD-DOWNS FOR ALTERNATE ( SHORT ) BRACED WALL PANELS. SEE R602.10.6 .

17. G.S.N., ALTERNATE / S201 ;I.C.B.O. NER-108 APPEARS TO BE NO LONGER AVAILABLE.

18. G.S.N., S201 ; THE U.B.C.IS NO LONGER IN FORCE.

19. G.S.N., SPECIAL INSPECTIONS ; PLEASE ADD EPOXY TO THE REQUIRED INSPECTIONS.

20. PROVIDE A CRICKET LAY-OUT AND SPEC THE SIZE OF THE ROOF DRAINS.

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS AND WEIGHTS..

2. PROVIDE COMBUSTION AND RELIEF AIR FOR THE WATER HEATERS. SEE THE STATE AMENDMENTS FOR THE U.P.C. AVAILABLE ON THE CITY'S WEB-SITE.

3. INCLUDE THE EXISTING PLUMBING FIXTURES IN THE FIXTURE SCHEDULE.

4. HOW DOES WATER SUPPLY GET TO WH-1?

5. IDENTIFY WH-2 ON THE SCHEMATICS.

6. JUSTIFY THE REDUCED SUPPLY AND DISCHARGES ON THE SCHEMATICS.

7. PLUMBING NOTE #7 / P101 ; CODE REFERENCE SHOULD BE THE U.P.C. AS ADOPTED.

8. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.




MECHANICAL PLANS:

1. GENERAL MECHANICAL NOTE #1 / M101 ; THE CODE REFERENCE SHOULD BE THE I.R.C.

2. GENERAL MECHANICAL NOTE #6 / M101 ; THE CONDENSATE CAN'T DRAIN INTO A VENT.

3. HOW DOES THE SUPPLY DUCT COMPLY WITH R1603?

ELECTRICAL PLANS:

1. PROVIDE A SMOKE DETECTOR IN THE AREA IMMEDIATELY OUTSIDE THE EXISTING SLEEPING ROOMS.

2. AT LEAST ONE WALL SWITCH CONTROLLED LIGHT OR OUTLET MUST BE PROVIDED IN ALL HABITABLE ROOMS PER E3803.2 . WHAT IS THE ROOM LOCATED EAST OF THE LIVING ROOM?

3. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.





IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110