Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00004
Parcel: 117062920

Address:
430 E 9TH ST

Review Status: Completed

Review Details: SITE

Permit Number - T04CM00004
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. Indicate a location map. D.S. 2-02.2.1.A.4

2. Indicate all existing buildings and structures, including roof slope and location of downspouts. D.S. 2-02.2.1.A.6 Sidewalks shall be flood free for all storm discharges of up to a ten (10) year flood event. Drainage flowing across all pedestrian circulation paths shall be conveyed under the path for up to ten (10) year frequency flood events. D.S. 2-08.3.1 & 4.1.E

3. Indicate existing length of sight visibility triangle. D.S. 2-02.2.1.A.10

4. If applicable, indicate location, type, size and height of existing and proposed signage. D.S. 2-02.2.1.A.13

5. Indicate limits of the 100-year floodplain and water surface elevation (when applicable). D.S. 2-02.2.1.A.15

6. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades. D.S. 2-02.2.1.A.16

7. Indicate estimated cut and fill quantities. D.S. 2-02.2.1.A.17

8. Indicate if streets are "Public or Private". D.S. 2-02.2.1.A.18

9. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. D.S. 2-02.2.1.A.23

10. Submit a signed letter from John Clark of Environmental Services indicating curbside pickup approval for a commercial site. D.S. 2-02.2.1.A.32
01/22/2004 JIM EGAN FIRE REVIEW Denied 1. Indicate fire rating/opening protectives for east and west exterior walls.
2. Indicate use and exterior wall fire rating for structure located adjacent to south property line.
01/28/2004 DAVID RIVERA HANDICAP-SITE REVIEW Denied See zoning comments under permit T04CM00002.
01/28/2004 DAVID RIVERA ZONING REVIEW Denied See zoning comments under permit T04CM00002.
01/29/2004 Joseph Linville NPPO REVIEW Approved See comments under permit T04CM00002.
01/29/2004 Joseph Linville LANDSCAPE REVIEW Denied See comments under permit T04CM00002.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2004 LISA LESNY OUT TO CUSTOMER Completed
01/30/2004 ANGIE SHOFFSTALL REJECT SHELF Completed