Permit Number: T04CM00003
Parcel: 117062930

Address:
428 E 9TH ST

Review Status: Completed

Review Details: SITE

Permit Number - T04CM00003
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. Indicate a location map. D.S. 2-02.2.1.A.4

2. Indicate all existing buildings and structures, including roof slope and location of downspouts. D.S. 2-02.2.1.A.6 Sidewalks shall be flood free for all storm discharges of up to a ten (10) year flood event. Drainage flowing across all pedestrian circulation paths shall be conveyed under the path for up to ten (10) year frequency flood events. D.S. 2-08.3.1 & 4.1.E

3. Indicate existing length of sight visibility triangle. D.S. 2-02.2.1.A.10

4. If applicable, indicate location, type, size and height of existing and proposed signage. D.S. 2-02.2.1.A.13

5. Indicate limits of the 100-year floodplain and water surface elevation (when applicable). D.S. 2-02.2.1.A.15

6. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades. D.S. 2-02.2.1.A.16

7. Indicate estimated cut and fill quantities. D.S. 2-02.2.1.A.17

8. Indicate if streets are "Public or Private". D.S. 2-02.2.1.A.18

9. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. D.S. 2-02.2.1.A.23

10. Submit a signed letter from John Clark of Environmental Services indicating curbside pickup approval for a commercial site. D.S. 2-02.2.1.A.32
01/22/2004 JIM EGAN FIRE REVIEW Denied Indicate fire rating/opening protectives for east, west, and south exterior walls.
01/28/2004 DAVID RIVERA HANDICAP-SITE REVIEW Denied See zoning comments under permit T04CM00002.
01/28/2004 DAVID RIVERA ZONING REVIEW Denied See zoning comments under permit T04CM00002.
01/29/2004 JOE LINVILLE NPPO REVIEW Approved See comments under permit T04CM00002.
01/29/2004 Joseph Linville LANDSCAPE REVIEW Denied See comments under permit T04CM00002.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2004 LISA LESNY OUT TO CUSTOMER Completed
01/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed