Permit Number: T04CM00002
Parcel: 117062940

Address:
426 E 9TH ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04CM00002
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2004 JIM EGAN FIRE REVIEW Denied 1. Indicate fire rating/opening protectives for east exterior wall. ( If using NJRC indicate so on plan. Plan indicates 2000 IBC.)
09/09/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed.

2. Submit a signed letter from John Clark of Environmental Services indicating curbside pickup approval for a commercial site. D.S. 2-02.2.1.A.32 Unable to locate attached letter pertaining to this comment. Resubmit letter or fax to my attention at 879-8010.

3. The submitted Floodplain Use Permit requires a Permit number issued and an "Ok to Submit" by the engineering staff. Attached to the F.U.P. is an Example of a cost estimate which needs to be signed by a licensed contractor and a print out of the Assessed Value of the structure. Resubmit F.U.P. with assign permit number along with the cost estimate by a licensed contractor and the assessed value of the structure.
09/14/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Provide a copy of the landscape plan cited in the decision letter for BOA Case # C10-01-32.

2) A 6' screen for refuse storage is required for adjacent properties LUC Table 3.7.2-I
10/06/2004 DAVID RIVERA HANDICAP-SITE REVIEW Denied see zoning comment number two.
10/06/2004 David Rivera ZONING REVIEW Denied DSC TRANSMITTAL

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T04CM00002
426 E. 9th Street
Administrative Office/Retail - Proposed uses
Site Plan

Transmittal date: 2nd Review October 6, 2004

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.



1. The previous comment stated that the three sites were reviewed as one site. Obviously this was not the intention because the site plan for the beauty salon is the only plan that was submitted for review. The following comments are specifically for the proposed beauty salon at address 426 E. 9th Street. Please address the comments and resubmit the revised site plan along with redline and response comments.

(Previous Comment: ***Note: This project will be reviewed as an overall site plan with three different uses. Although an extension has been granted for the Board of Adjustment case C10-01-32 the plan submitted for review does not address the two new uses, Personal Service Use; Beauty Salon and Residential Use: Multifamily apartments. The plan must be revised to include all required LUC data information for each one of the proposed uses.)

I have also been made aware that an additional Board of Adjustment case decision is pending. Both Board of Adjustment case numbers, date of approvals, and conditions of approval must be listed on the plan unless the new supercedes the previous case. Additional comments may be forthcoming due to conditions of approval for the B. of A.

2. The previous comment related to the sidewalk was based on the three sites functioning as one overall commercial site. I acknowledge that a sidewalk has been provided on Hoff to provide access to the building. What is not labeled on the plan is whether the sidewalk is accessible route that meets maximum allowed slope of 12: 1. Steps or stairs anywhere within the sidewalk area proposed accessibility is allowed unless a separate ramp with railing if necessary is provided next to the accessible route. Demonstrate on the plan how this requirement will comply.

(Previous Comment: In addition to the required sidewalk as shown on the plan the three sites must be provided with an accessible route that meets ADA compliance. The accessible route may be the same route as the existing or proposed sidewalks as long as the sidewalks meet the minimum slope requirements of 12:1. Stairs will not meet the requirements. The accessible route may be placed in a different location but must connect to onsite circulation that leads the pedestrian to the building.)

Also per DS 2-08.4.1.A, a concrete sidewalk that provides pedestrian access from Hoff Avenue to the site must be provided and must interconnect to the onsite pedestrian circulation/sidewalk. All sidewalks must be a minimum of four feet wide. Dimension the width of the sidewalks, demonstrate onsite circulation for address 426, and 430 and label the construction material for the sidewalks, concrete, pavers, brick etc. DS 2-02.2.1.A.

3. I have discussed the proposed Personal Service use: Beauty Salon with Wayne Bogdan. Per our discussion related to the previous Board of Adjustment approval the case was reviewed and variances granted based on proposed Office and Retail uses. Per Wayne, this proposed use must go back to the Board of Adjustment for consideration. Zoning will not approve the plan until resolution or a new Board of Adjustment approval has been granted. Call Wayne Bogdan at 791-4541 for more information on the process and his determination.

(Prior approvals such as Board of Adjustment must be listed on the plan. The case number, the variances requested, the variances approved, and the conditions of approval must be listed. A copy of the most recent B. of A. Notice of Decision letter must be submitted with the subsequent submittal. DS 2-02.2.1.A.38)

.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and landscape plan and requested documents.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2004 DELMA ROBEY OUT TO CUSTOMER Completed