Permit Number: T04CM00002
Parcel: 117062940

Address:
426 E 9TH ST

Review Status: Completed

Review Details: SITE

Permit Number - T04CM00002
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. Indicate a location map. D.S. 2-02.2.1.A.4

2. Indicate all existing buildings and structures, including roof slope and location of downspouts. D.S. 2-02.2.1.A.6 Sidewalks shall be flood free for all storm discharges of up to a ten (10) year flood event. Drainage flowing across all pedestrian circulation paths shall be conveyed under the path for up to ten (10) year frequency flood events. D.S. 2-08.3.1 & 4.1.E

3. Indicate existing length of sight visibility triangle. D.S. 2-02.2.1.A.10

4. If applicable, indicate location, type, size and height of existing and proposed signage. D.S. 2-02.2.1.A.13

5. Indicate limits of the 100-year floodplain and water surface elevation (when applicable). D.S. 2-02.2.1.A.15

6. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades. D.S. 2-02.2.1.A.16

7. Indicate estimated cut and fill quantities. D.S. 2-02.2.1.A.17

8. Indicate if streets are "Public or Private". D.S. 2-02.2.1.A.18

9. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. D.S. 2-02.2.1.A.23

10. Submit a signed letter from John Clark of Environmental Services indicating curbside pickup approval for a commercial site. D.S. 2-02.2.1.A.32

11. Delineate 100-year FEMA floodplain.
01/22/2004 JIM EGAN FIRE REVIEW Denied 1. Indicate fire rating/opening protectives for east exterior wall.
01/26/2004 David Rivera HANDICAP-SITE REVIEW Denied See zoning comment #3.
01/26/2004 David Rivera ZONING REVIEW Denied DSC TRANSMITTAL

FROM: David Rivera Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T04CM00003
428 E. 9th Street
Administrative Office/Retail - Proposed uses
Site Plan

Transmittal date: 1st Review January 26, 2004

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. ***Note: This project will be reviewed as an overall site plan with three different uses. Although an extension has been granted for the Board of Adjustment case C10-01-32 the plan submitted for review does not address the two new uses, Personal Service Use; Beauty Salon and Residential Use: Multifamily apartments. The plan must be revised to include all required LUC data information for each one of the proposed uses.

I have also been made aware that an additional Board of Adjustment case decision is pending. Both Board of Adjustment case numbers, date of approvals, and conditions of approval must be listed on the plan unless the new supercedes the previous case. Additional comments may be forthcoming due to conditions of approval for the B. of A.

The new uses must meet full code compliance as it relates to the Land Use Code and Development Standards that are applicable to the three new uses. Requirements that have been addressed by both B. of A. cases will not be commented on but must comply with the plan dated May 31, 2001. Please provide a copy of the May 31 2001 plan for reference with the subsequent submittal packet. Please address the following comments as required.

2. A small, project-location map shall be drawn on the first sheet of the site plan, preferably in the upper right corner. The map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information.
a. Show the subject property approximately centered within the one (1) square mile area.
b. Identify conditions within the square mile area, such as major streets and watercourses.
c. Section, township, and range; section corners; north arrow; and the scale will be labeled.
DS 2-02.2.1.A.4

3. In addition to the required sidewalk as shown on the plan the three sites must be provided with an accessible route that meets ADA compliance. The accessible route may be the same route as the existing or proposed sidewalks as long as the sidewalks meet the minimum slope requirements of 12:1. Stairs will not meet the requirements. The accessible route may be placed in a different location but must connect to onsite circulation that leads the pedestrian to the building.

Also per DS 2-08.4.1.A, a concrete sidewalk that provides pedestrian access from Hoff Avenue to the site must be provided and must interconnect to the onsite pedestrian circulation/sidewalk. All sidewalks must be a minimum of four feet wide. Dimension the width of the sidewalks, demonstrate onsite circulation for address 426, and 430 and label the construction material for the sidewalks, concrete, pavers, brick etc. DS 2-02.2.1.A.

4. Indicate the location of existing or proposed freestanding signage. The size type and location must be labeled. DS 2-02.2.1.A.13

5. If applicable indicate the location and type of existing or proposed freestanding lighting. DS 2-02.2.1.A.25

6. List on the plan the legal existing uses for each of the parcels. DS 2-02.2.1.A.31

7. Prior approvals such as Board of Adjustment must be listed on the plan. The case number, the variances requested, the variances approved, and the conditions of approval must be listed. A copy of the most recent B. of A. Notice of Decision letter must be submitted with the subsequent submittal. DS 2-02.2.1.A.38

8. List on the plan for each parcel the specific use and development designator, along with any applicable LUC subject to section numbers, the allowed and proposed floor area ratio, and lot coverage. DS 2-02.2.2.A.1-.6

9. If the three sites will work as one site the onsite pedestrian circulation must interconnect.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and landscape plan and requested documents.
01/29/2004 Joseph Linville NPPO REVIEW Approved Exception per 2002 PC aerial photo.
01/29/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Provide a copy of the landscape plan cited in the decision letter for BOA Case # C10-01-32.

2) Indicate the location of any areas reserved for storage of refuse containers. These areas are to be screened from adjacent properties and streets in compliance with LUC Table 3.7.2-I.

3) Provide dust control for the entire site in compliance with LUC 3.7.2.7.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2004 LISA LESNY OUT TO CUSTOMER Completed
01/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed