Permit Number: T04BU03047
Parcel: 115154130

Review Status: Completed

Review Details: OTHER

Permit Number - T04BU03047
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2005 BLANCA ESPINO ENGINEERING REVIEW Denied assignment per JPV
02/25/2005 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. The Drainage Report has been reviewed and approved as part of the Floodplain Use Permit review.

3. Sight Visibility Triangles are clear lines of sight will be maintained along all streets and driveways to assure the safety of motorists and pedestrians. D.S.3-01.5.1 Lines of sight will not be obscured between thirty (30) inches and six (6) feet through a triangular area adjacent to a driveway, a PAAL, an alley, or a street, where such access ways intersect with another street in a T-configuration. D.S.3-01.5.1.A.1

4. The proposed retaining wall exceeds the required height for a Sight Visibility Triangle. Correct and revise or contact Matthew Flick of Development Services/Engineering @ 791-5640 ext. 1192 to reach an agreement that does not meet Development Standards 3-01.5.0 and to obtain a DSMR.

5. Correct and revise Structural Calculations to indicate changes as per comment #4.
03/15/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T04BU03047 .. 2075 N CALLE CENTRAL .. 1ST REVIEW .. DGL .. 3/16/05 ..

S1. Clarify location of retaining wall on site plan C1.0, by dimension from adjacent property lines.
S2. Provide elevation of retaining wall, showing grades, length of wall, and daylighting of drain.
S3. Provide information required for design of Allan Block Retaining Wall System, ER-5087:
1. Foundation investigation.
2. Federal Highway Administration - Design and Construction Guidelines for Reinforced Soil Structures, Volume I .
3. Allan Block Retaining Walls Design Manual.
4. Provide structural calculations to comply with the ER Report #5087, including global stability and reinforcing requirements.
S4. Clarify on drawings, per ER5087, Special Inspection required for:
1. Block placement.
2. Backfill.
3. Geogrid installation, if required by structural calculations.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
03/25/2005 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2005 DELMA ROBEY OUT TO CUSTOMER Completed