Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04BU03026
Parcel: Unknown

Address:
2921 E ALLEN RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T04BU03026
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2005 MATT FLICK ENGINEERING REVIEW Approved Previous comments addressed.
05/25/2005 DAVID RIVERA ZONING REVIEW Approved
05/26/2005 ANDREW CONNOR NPPO REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
06/07/2005 SUE REEVES APPROVAL SHELF Completed
06/07/2005 JMORALE1 OUT TO CUSTOMER Completed