Permit Number: T04BU03025
Parcel: Unknown

Address:
3010 W ANKLAM RD

Review Status: Completed

Review Details: OTHER

Permit Number - T04BU03025
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Codes and references per the 2003 IBC
2) Provide Special Inspection form for all retaining walls exceeding 4'-0".
3) General Notes - Per Note #10 a Special Inspection form is required for Foundation / Excavation.
4) Details on sht. C1.5 and C1.6 locations should be shown on C1.2.
5) Where is Appendix 'A' referenced on sht. 12/34 of structural calculations.
6) Clarify on details per sht. 12 of soils report fill materials note #2 - select granular materials should be used as backfill behind walls which retain earth.
7) Provide elevations of walls shown on site plan and designate location of each wall detail.
8) Rebar specified on calculations sht. 17 does not match detail S& V on sht. C1.5.
9) Detail 'U' sht. C1.5 and structural calculations page 24. Please clarify location of #5 rebar @ 12" o.c. at base wall.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/18/2005 BETH GRANT OUT TO CUSTOMER Completed
02/18/2005 ANGIE SHOFFSTALL REJECT SHELF Completed