Permit Number: T04BU02978
Parcel: 116094060

Address:
2945 W SALVIA DR

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU02978
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2005 Elizabeth Eberbach ENGINEERING REVIEW Denied TO: Carl Ewing RA
SUBJECT: Montage Vista II Lot 58 Grading Review
REVIEWER: Elizabeth Eberbach
DATE: January 10, 2005
ACTIVITY NUMBERS: T04BU02978

SUMMARY: Engineering Division of Development Services Department has received and reviewed the Grading Plan submittal and permit application for lot 58 and does not recommend approval of this grading plan at this time. Address the following comments:

GRADING PLAN COMMENTS:
1) Development Standards (DS) Section 11-01.4.1.C.3: On sheet G-1, provide grading limit delineation around the area of proposed disturbance; disturbance is limited to proposed amenities and construction area. Remove "Grading Limit" text adjacent to preservation fence, or clarify as the maximum grading limit not used for this project. See redlines.
2) DS Sec.11-01.9.3.B: Provide slope setback at north boundary for construction area of retaining wall footer as well as temporary stormwater runoff controls to prevent disturbance of adjacent lot. Dimension distance to grading limits to clarify construction area for footer and dimension to footer as well as to wall from property line. See redlines.
3) DS Sec.11-01.4.1.C.3: On sheet G-1, locate cross section detail 3 adjacent to the most restrictive section adjacent to proposed building, and clarify the following for detail 3 on sheet G-2 (see redlines):
a) Show utility unit and edge of building;
b) Show and label minimum dimension from edge of building to center flowline of swale;
c) Label dimensions for slope and interceptor swale;
d) Show and label grading limits and Property line;
4) DS Sec.3-01.2.1.A: Show general locations of proposed utility lines from pedestals to house.
5) DS Sec.11-01.9.2: On sheet G-1, provide interceptor swale and location of grade break for flows on the top of the cut slope near the south boundary. See redlines.
6) DS Sec.11-01.4.1.C.3: Clarify the following:
a) Clarify cross section detail A-A on sheet G-2; show grading limit.
b) On sheet G-1, provide maximum dimension for the extent of cut/fill for rear yard; see redlines.
c) On sheet G-1, clarify keynote numbers 1-3 as being on a separate sheet.
7) DS Sec.9-04.3.1.B.5: Provide the Geotechnical Report that addresses the proposed exposed cut slope at the south boundary and any other recommendations.

For resubmittal, provide 3 copies of the revised grading plans, a copy of the geotechnical report, redlines, a response letter addressing all comments, and any other supplemental documents. If you have any questions, I can be reached at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Section
Development Services
01/24/2005 MICHAEL ST. PAUL ZONING REVIEW Needs Review Engineering approval and a viable site plan are required for zoing review.
12/17/2004 Andrew Connor NPPO REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/24/2005 ANGIE SHOFFSTALL REJECT SHELF Completed