Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04BU02900
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2005 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) Sheet 35 of calc`s shows the reaction at the supports, specify the sheet in calc`s where those reactions appear and highlight those numbers. Do the same for the joints. 2) Do the same for sheet 59 for the loads and moments, 2830,4371, 1197, and 4556 show where they appear in the analysis and highlight. 3) Sheet 63 shows an allowable soil pressure of 2830 psf. which exceeds the allowable of 1500 psf. What is being done to correct it? 4) Where in the calc`s is the design for the 4-#12 screws shown on sheet D-1? |
| 12/02/2004 | Jim Egan | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/10/2005 | BETH GRANT | REJECT SHELF | Completed |